Effect of the Activities Inside a Hospital Theatre of its IAQ

dc.contributor.authorGunaratne, WDSP
dc.contributor.authorGunatilake, MMDV
dc.contributor.authorJayasinghe, C
dc.contributor.authorMadushanka, HKR
dc.contributor.authorPerera, TM
dc.contributor.authorPerera, SAS
dc.contributor.authorRajapaksa, S
dc.date.accessioned2016-05-26T07:04:38Z
dc.date.available2016-05-26T07:04:38Z
dc.date.issued2016-05-26
dc.description.abstractA close relationship can be observed between the building performance and the activities associated with the building. Since those activities have a great impact on Indoor Air Quality (IAQ) of the building, it is necessary to consider the activities that would take place inside a building, at its design stage. In this research study, the effect of the activities associated with a hospital theatre, on its IAQ has been studied since the theatre staff of a leading hospital in Sri Lanka, experience some discomfort while being inside the theatre. In order to evaluate this, variation of Carbon Dioxide (CO2), Carbon Monoxide (CO), Total Volatile Organic Compounds (TVOC) and Particulate Matter less than 2.5 microns (PM2.5) concentrations inside the theatre were measured and analysed. Significant variations were observed in the concentrations of CO2, TVOC and CO inside the operation theatre. CO2 concentration inside the room increased at the beginning and end of the surgeries due to high occupant density and also during Laparoscopic surgeries. TVOC concentration was affected by the usage of different chemicals during the surgery. Major effect to the CO concentration was by Diathermy.en_US
dc.identifier.departmentDepartment of Civil Engineeringen_US
dc.identifier.emailgunaratne.sanduni@gmail.comen_US
dc.identifier.emaildhanuvida@yahoo.comen_US
dc.identifier.emailchintha@civil.mrt.ac.lken_US
dc.identifier.emailhkrumesh@gmail.comen_US
dc.identifier.emailmanori2007@gmail.comen_US
dc.identifier.emailanul@cheng.mrt.ac.lken_US
dc.identifier.emailsamadhirajapaksa@yahoo.comen_US
dc.identifier.facultyEngineeringen_US
dc.identifier.urihttp://dl.lib.mrt.ac.lk/handle/123/11765
dc.language.isoenen_US
dc.subjectIndoor Air Quality (IAQ)en_US
dc.subjectHospital theatre
dc.subjectSick Building Syndrome (SBS)
dc.titleEffect of the Activities Inside a Hospital Theatre of its IAQen_US
dc.typeConference-Full-texten_US

Files